Vevor CY knob LCD: single-digit fault numbers

Updated

Vevor's CY manual documents two knob LCDs that show a bare fault digit, and their tables differ from each other as well as from every E-code table. Work out which of the two you have from its keys before you look a number up.

Is this your controller?

E-01

Also called: Vevor knob controller, plateau-key controller

An LCD with a knob button on Vevor CY-5001, CY-5002 and CY-5004 heaters. One version has a knob plus an oil pump key and a plateau (altitude) key; the other has a single knob button. Faults appear as a bare digit with no E.

How it shows a fault: A single digit. The two versions number their faults differently: on the knob-with-keys version 3 is the fuel pump and 4 the glow plug; on the single-knob version 2 is the fuel pump and 3 the glow plug.

Reported on: Vevor CY-5001, Vevor CY-5002, Vevor CY-5004.

Not a match? See the other controller families.

At a glance

Fault displayA bare digit (1 to 9) with no E, on a Vevor knob LCD
Codes documented2, 3, 4, 5, 6, 7, 8, 9, 1
Settings menuSingle-knob version: hold the knob 3 s while shut down to step through voltage, temperature, manual pumping and remote items
Remote pairingNot documented in our sources

Error codes on this controller

CodeControllerManual or brandMeaningStated limit
1Vevor CY knob LCDVevor CY, single-knob LCD
Manual
Power supply voltage out of range
Manual's remedy: Check the battery or generator; check whether the fuse is aged.
Normal range: 24 V controller 18-32 V; 12 V controller 9-16 V
2Vevor CY knob LCDVevor CY, knob LCD with pump and plateau keys
Manual
Power supply voltage out of range
Manual's remedy: Check whether the battery or generator is normal.
Normal range: 24 V controller 18-32 V; 12 V controller 9-16 V
2Vevor CY knob LCDVevor CY, single-knob LCD
Manual
Oil (fuel) pump failure
Manual's remedy: Check pump wire and connector for damage, looseness, oxidation, short or open circuit.
Not stated
3Vevor CY knob LCDVevor CY, knob LCD with pump and plateau keys
Manual
Oil (fuel) pump failure
Manual's remedy: Check pump connections and connectors for damage or looseness.
Not stated
3Vevor CY knob LCDVevor CY, single-knob LCD
Manual
Ignition plug malfunction
Manual's remedy: Check whether the plug is damaged and whether its connector is loose/oxidised or the wire is short/open.
Not stated
4Vevor CY knob LCDVevor CY, knob LCD with pump and plateau keys
Manual
Ignition plug failure
Manual's remedy: Check whether the ignition plug connector is loose.
Not stated
4Vevor CY knob LCDVevor CY, single-knob LCD
Manual
Fan failure
Manual's remedy: Check whether the impeller is stuck; connector loose or oxidised; magnet-to-Hall-sensor gap too large or magnet installed reversed; short/open circuit or motor coil leakage.
Not stated
5Vevor CY knob LCDVevor CY, knob LCD with pump and plateau keys
Manual
Fan failure
Manual's remedy: Check whether the impeller is stuck; check whether the connector is loose.
Not stated
5Vevor CY knob LCDVevor CY, single-knob LCD
Manual
High temperature alarm
Manual's remedy: Check the heating duct is clear; fan operates normally; temperature sensor normal.
Air inlet above 50 C; enclosure above 230 C
6Vevor CY knob LCDVevor CY, knob LCD with pump and plateau keys
Manual
Sensor failure
Manual's remedy: Check whether temperature sensor wires/connectors are damaged or loose and whether the sensor is damaged.
Not stated
6Vevor CY knob LCDVevor CY, single-knob LCD
Manual
Flameout alarm
Manual's remedy: Check for fuel shortage, frozen fuel circuit or stuck pump; check combustion intake and exhaust ducts; check the casing temperature sensor is in full contact with the casing.
Not stated
7Vevor CY knob LCDVevor CY, knob LCD with pump and plateau keys
Manual
Unsuccessful startup
Manual's remedy: 1) Shell temperature too high. 2) Lots of white smoke: check fan, filter beside the ignition plug, combustion intake/exhaust passages, ignition plug ageing. 3) Little or no white smoke: check fuel shortage, frozen fuel line, blocked pump, damaged ignition plug, loose housing temperature sensor.
Shell too hot to be cooled within 3 minutes after starting (cause 1)
7Vevor CY knob LCDVevor CY, single-knob LCD
Manual
Unsuccessful startup
Manual's remedy: 1) Casing too hot and not cooled after 3 minutes of start-up. 2) Lots of white smoke in exhaust: check the filter screen next to the ignition plug (clean/replace), whether the pump sprays fuel forcefully, whether the ignition plug is aged. 3) Little or no white smoke: check for fuel shortage, frozen or blocked fuel circuit, pump stuck/damaged, combustion intake and exhaust clear, ignition plug damaged, inner fan-wheel clearance too large. 4) Ignites normally but still reports ignition failure: check the casing temperature sensor is in full contact with the casing, its pressure spring, and the sensor itself.
Casing cannot be cooled after 3 minutes of start-up (cause 1)
8Vevor CY knob LCDVevor CY, knob LCD with pump and plateau keys
Manual
High temperature alarm
Manual's remedy: Check the heating duct is unobstructed; check the fan works properly.
Intake above 50 C; casing above 200 C
8Vevor CY knob LCDVevor CY, single-knob LCD
Manual
Sensor failure
Manual's remedy: Check whether the temperature sensor wire/connector is damaged or loose and whether the sensor is damaged.
Not stated
9Vevor CY knob LCDVevor CY, knob LCD with pump and plateau keys
Manual
Flameout alarm
Manual's remedy: Check for fuel shortage, frozen fuel line, jammed pump; check the fan works properly.
Not stated

Procedures on this controller

Prime the fuel line (version with oil pump key) Manual

With the heater shut down, long-press the oil pump key for two seconds to pump manually; release to stop.

Stop when fuel reaches the heater.

Full guide

Plateau (high-altitude) mode (version with plateau key) Manual

Long-press the plateau key for 2 s to enter plateau mode, which leans the mixture for thin air. Long-press again for 2 s to leave it.

Full guide

Known quirks

  • The same manual also covers two LCD panels that show E-2 to E-10 and an LED-bar dial that flashes its faults. One heater model number can ship with any of the five.
  • The high temperature alarm limit is casing above 200 °C on the knob-with-keys version and above 230 °C on the single-knob version.